141
P2.15
Drop control
Setting Range
:
0.00Hz
~
10.00Hz
0
This function is used for balancing the workload allocation when multiple motors are used to
drive the same load. The output frequency of the AC drives decreases as the load
increases.
You can reduce the workload of the motor under load by
decreasing the output frequency for this motor, implementing
workload balancing between multiple motors.
P2.16
Accumulative power-on
time threshold
Setting Range
:
0h
~
65000h
0
If the accumulative power-on time (P7.12) reaches the value set
in this parameter, the corresponding DO terminal becomes ON.
P2.17
Accumulative running
time threshold
Setting Range
:
0h
~
65000h
0
It is used to set the accumulative running time threshold of the AC drive. If the accumulative
running time (P7.08) reaches the value set in this parameter, the corresponding DO terminal
becomes ON.
P2.18
Startup protection
Setting Range
:
0
~
1
0
0
:
NO
;
1
:
YES
This parameter is used to set whether to enable the safety protection. If it is set to 1, the AC
drive does not respond to the run command valid upon AC drive power-on (for example, an
input terminal is ON before power-on). The AC drive responds only after the run command
is cancelled and becomes valid again.