are disabled.
When the dormant function is enabled, if the frequency source is
PID, whether PID operation is performed in the dormant state is
determined by P6.28. In this case, select PID operation enabled
in the stop state (P6.28 = 1).
P2.51
Current running time
reached
Setting Range
:
0.0s
~
6500.0s
0.0s
If the current running time reaches the value set in this parameter, the corresponding DO
becomes ON, indicating that the current running time is reached.
6.4 Input Terminals
(
Group P3
)
P3.00
X1 function selection
Setting range
:
0
~
50
1
P3.01
X2 function selection
Setting range
:
0
~
50
2
P3.02
X3 function selection
Setting range
:
0
~
50
9
P3.03
X4 function selection
Setting range
:
0
~
50
12
P3.04
X5 function selection
Setting range
:
0
~
50
13
P3.05
X6 function selection
Setting range
:
0
~
50
0
P3.06
X7 function selection
Setting range
:
0
~
50
0
P3.07
X8 function selection
Setting range
:
0
~
50
0
P3.08
X9 function selection
Setting range
:
0
~
50
0
P3.09
X10 function selection
Setting range
:
0
~
50
0
Terminal X1~X10 provide rich functions, user can select it as required by set P3.00 to
P3.09.For details, see following table 6-1,and X1 to terminal FWD,X2 to terminal REV.
Table 6-1 Functions of XI terminals