236
E-32 User defined
fault 1
Input user defined fault 1 signal
via multi-function terminal X
Reset
E-33 User defined
fault 2
Input user defined fault 2 signal
via multi-function terminal X
Reset
E-34 Contactor
fault
Drive board or power supply is
abnormal
Change drive board or power supply
Contactor is abnormal
Change contactor
E-35 Short circuit to
ground fault
Motor short circuit to ground
Change motor or cable
7.2 Fault Record Search
Inverter record the fault codes occurred in the last 3 times. The fault information is reserved
in PA group. Enter PA parameter group by Keypad operation
7.3 Fault Reset
When fault occurred, please select the following methods to recover:
(1) When fault code is displayed, after ensure it can be reset, press key to reset.
(2) Set one of X1~X8 terminal as external RESET input (P3.00~P3.09=9).
(3) Cut off power.