Troubleshooting:
Compare the output current shown on the LCP
with the frequency converter rated current.
Compare the output current shown on the LCP
with measured motor current.
Display the Thermal Drive Load on the LCP and
monitor the value. When running above the
frequency converter continuous current rating,
the counter should increase. When running below
the frequency converter continuous current
rating, the counter should decrease.
NOTICE
See the derating section in the Design Guide for more
details, if a high switching frequency is required.
WARNING/ALARM 10, Motor overload temperature
According to the electronic thermal protection (ETR), the
motor is too hot. Select whether the frequency converter
gives a warning or an alarm when the counter reaches
100% in
. The fault is that the
motor is overloaded by more than 100% for too long.
Troubleshooting:
Check if motor is over heating.
If the motor is mechanically overloaded
That the motor
is set correctly.
Motor data in parameters 1-20 through 1-25 are
set correctly.
Run AMA in
1-29 Automatic Motor Adaption (AMA)
.
WARNING/ALARM 11, Motor thermistor over temp
The thermistor or the thermistor connection is discon-
nected. Select whether the frequency converter gives a
warning or an alarm in
Troubleshooting:
Check if motor is over heating.
Check if the motor is mechanically overloaded.
Check that the thermistor is connected correctly.
If using a thermal switch or thermistor, check the
programming of
matches
sensor wiring.
WARNING/ALARM 13, Over current
The inverter peak current limit is exceeded. The warning
lasts about 1.5 s, then the frequency converter trips and
issues an alarm.
Troubleshooting:
This fault may be caused by shock loading or fast
acceleration with high inertia loads.
Turn off the frequency converter. Check if the
motor shaft can be turned.
Check that the motor size matches the frequency
converter.
Incorrect motor data in parameters 1-20 through
1-25.
ALARM 14, Earth (ground) fault
There is a discharge from the output phases to earth,
either in the cable between the frequency converter and
the motor or in the motor itself.
Troubleshooting:
Turn off the frequency converter and remove the
earth fault.
Measure the resistance to ground of the motor
leads and the motor with a megohmmeter to
check for earth faults in the motor.
ALARM 16, Short circuit
There is short-circuiting in the motor or on the motor
terminals.
Turn off the frequency converter and remove the short-
circuit.
WARNING/ALARM 17, Control word timeout
There is no communication to the frequency converter.
The warning is only active when
is NOT set to OFF.
If
is set to
Stop
and
Trip
, a
warning appears and the frequency converter ramps down
until it trips, while giving an alarm.
Troubleshooting:
Check connections on the serial communication
cable.
Increase
Check operation of the communication
equipment.
Verify proper installation based on EMC
requirements.
WARNING 24, Fan fault
The fan warning function is an extra protection function
that checks if the fan is running/mounted. The fan warning
can be disabled in
([0] Disabled).
Troubleshooting:
Check fan resistance.
ALARM 30, Motor phase U missing
Motor phase U between the frequency converter and the
motor is missing.
Turn off the frequency converter and check motor phase
U.
ALARM 31, Motor phase V missing
Motor phase V between the frequency converter and the
motor is missing.
Turn off the frequency converter and check motor phase V.
Troubleshooting
VLT
®
HVAC Basic Drive FC 101 Programming Guide
MG18B302 - Rev. 2013-09-02
85
4
4
Summary of Contents for VLT HVAC Basic Drive FC 101
Page 2: ......
Page 104: ...www danfoss com drives MG18B302 130R0221 MG18B302 Rev 2013 09 02...