![background image](http://html1.mh-extra.com/html/danfoss/vlt-hvac-basic-drive-fc-101/vlt-hvac-basic-drive-fc-101_programming-manual_3682341019.webp)
Motor Set-up
The Quick Menu Motor Set-up guides through the needed motor parameters.
Parameter
Range
Default
Function
[0] International
[1] US
0
[0] -[132] see start -up wizard for
open loop application
Size selected
Select operating mode for restart
upon reconnection of the frequency
converter to mains voltage after
power down
*[0] Motor construction
[1] PM, non salient SPM
[0] Asynchron
0.12-110 kW/0.16-150 hp
Size related
Enter motor power from nameplate
data
50.0-1000.0 V
Size related
Enter motor voltage from nameplate
data
20.0-400.0 Hz
Size related
Enter motor frequency from
nameplate data
0.01-10000.00 A
Size related
Enter motor current from nameplate
data
100.0-9999.0 RPM
Size related
Enter motor nominal speed from
nameplate data
1-26 Motor Cont. Rated Torque 0.1-1000.0
Size related
This parameter is available only when
Design is set
to
[1] PM, non-salient SPM
.
NOTICE
Changing this parameter affects
settings of other parameters
0.000-99.990
Size related
Set the stator resistance value
0-1000
Size related
Enter the value of the d-axis
inductance.
Obtain the value from the permanent
magnet motor data sheet. The de-axis
inductance cannot be found by
performing an AMA.
2-100
4
Enter the number of motor poles
10-9000
Size related
Line-Line RMS back EMF voltage at
1000 RPM
1-73 Flying Start
[0] Disabled
[1] Enabled
0
Select
[1] Enable
to enable the
frequency converter to catch a
spinning motor
0.05-3600.0 s
Size related
Ramp up time from 0 to rated
3-42 Ramp 1 Ramp Down Time 0.05-3600.0 s
Size related
Ramp down time from rated
to 0
4-12 Motor Speed Low Limit
[Hz]
0.0-400 Hz
0.0 Hz
Enter the minimum limit for low
speed
4-14 Motor Speed High Limit
[Hz]
0.0-400 Hz
65
Enter the maximum limit for high
speed
0-400
Size related
Enter the maximum output frequency
value
Table 2.6 Motor Parameters