3 Parameters
3.1 Main Menu - Operation and Display -
Group 0
Parameters related to the fundamental functions of the
frequency converter, function of the LCP keys and configu-
ration of the LCP display.
3.1.1 0-0* Basic Settings
0-01 Language
Option:
Function:
Defines the language to be used in the display.
[0]
*
English
[1]
Deutsch
[2]
Francais
[3]
Dansk
[4]
Spanish
[5]
Italiano
[28]
Bras.port
[255] No Text
0-03 Regional Settings
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
To meet the needs for different default settings
in different parts of the world,
is implemented in the frequency
converter. The selected setting influences the
default setting of the motor nominal frequency.
[0] Interna-
tional
Sets default value of
[50
Hz].
[1] North
America
Sets the default value of
to
60 Hz.
0-04 Operating State at Power-up
Option:
Function:
Select the operating mode upon reconnection of
the frequency converter to mains voltage after
power down when operating in Hand (local)
mode.
[0]
*
Resume
Resumes operation of the frequency converter
maintaining the same local reference and the
same start/stop condition (applied by [Hand On]/
[Off] on the LCP or Hand Start via a digital input
0-04 Operating State at Power-up
Option:
Function:
as before the frequency converter was powered
down.
[1]
Forced
stop,
ref=old
Uses saved reference [1] to stop the frequency
converter but at the same time retain the local
speed reference in memory before powering
down. After mains voltage is reconnected and
after receiving a start command (pressing [Hand
On] key or using her Hand Start command via a
digital input) the frequency converter restarts
and operates at the retained speed reference.
0-06 GridType
Option:
Function:
Select the grid type of the supply
voltage/frequency.
NOTICE
Not all choices are supported
in all power sizes.
IT grid is a supply mains, where
there are no connections to
ground.
Delta is a supply mains where the
secondary part of the transformer
is delta connected and one phase
is connected to ground.
[0]
200-240V/50Hz/IT-grid
[1]
200-240V/50Hz/Delta
[2]
200-240V/50Hz
[10]
380-440V/50Hz/IT-grid
[11]
380-440V/50Hz/Delta
[12]
380-440V/50Hz
[20]
440-480V/50Hz/IT-grid
[21]
440-480V/50Hz/Delta
[22]
440-480V/50Hz
[30]
525-600V/50Hz/IT-grid
[31]
525-600V/50Hz/Delta
[32]
525-600V/50Hz
[100] 200-240V/60Hz/IT-grid
[101] 200-240V/60Hz/Delta
[102] 200-240V/60Hz
[110] 380-440V/60Hz/IT-grid
[111] 380-440V/60Hz/Delta
[112] 380-440V/60Hz
[120] 440-480V/60Hz/IT-grid
[121] 440-480V/60Hz/Delta
[122] 440-480V/60Hz
[130] 525-600V/60Hz/IT-grid
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
20
MG18B302 - Rev. 2013-09-02