[80]
SL Digital
Output A
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action
[38] Set dig. out. A high
is
executed. The input goes low whenever
the Smart Logic Action
[32] Set dig. out. A
low
is executed.
[81]
SL Digital
Output B
See
13-52 SL Controller Action
. The input
goes high whenever the Smart Logic
Action
[39] Set dig. out. B high
is
executed. The input goes low whenever
the Smart Logic Action
[33] Set dig. out. B
low
is executed.
[82]
SL Digital
Output C
See
13-52 SL Controller Action
. The input
goes high whenever the Smart Logic
Action
[40] Set dig. out. C high
is
executed. The input goes low whenever
the Smart Logic Action
[34] Set dig. out. C
low
is executed.
[83]
SL Digital
Output D
See
13-52 SL Controller Action
. The input
goes high whenever the Smart Logic
Action
[41] Set dig. out. D
high is
executed. The input goes low whenever
the Smart Logic Action
[35] Set dig. out.
D low
is executed.
[84]
SL Digital
Output E
See
13-52 SL Controller Action
. The input
goes high whenever the Smart Logic
Action
[42] Set dig. out. E high
is
executed. The input goes low whenever
the Smart Logic Action
[36] Set dig. out. E
low
is executed.
[85]
SL Digital
Output F
See
13-52 SL Controller Action
. The input
goes high whenever the Smart Logic
Action
[43] Set dig. out. F high
is
executed. The input goes low whenever
the Smart Logic Action
[37] Set dig. out. F
low
is executed.
[160] No alarm
The output is high when no alarm is
present.
[161] Running reverse The output is high when the frequency
converter runs counter clockwise (the
logical product of the status bits
‘running’ AND ‘reverse’).
[165] Local reference
active
The output is high when
3-13 Reference
Site
=
[2] Local
or when
3-13 Reference
Site
=
[0] Linked to hand auto
at the
same time as the LCP is in [Hand On]
mode.
[166] Remote
reference active
The output is high when
3-13 Reference
Site
[1] or Linked to hand/auto [0]
while
the LCP is in [Auto on] mode.
[167] Start command
active
The output is high when there is an
active Start command (i.e. via digital
input bus connection or [Hand on] or
[Auto on], and no Stop command is
active.
[168] Drive in hand
mode
The output is high when the frequency
converter is in Hand on mode (as
indicated by the LED light above [Hand
on].
[169] Drive in auto
mode
The output is high when the frequency
converter is in Hand on mode (as
indicated by the LED light above [Auto
on].
[180] Clock Fault
The clock function has been reset to
default (2000-01-01) because of a power
failure.
[181] Preventive
Maintenance
One or more of the Preventive
Maintenance Events programmed in
23-10 Maintenance Item
has passed the
time for the specified action in
23-11 Maintenance Action
.
[193] Sleep Mode
The frequency converter/system has
turned into sleep mode. See parameter
group
22-4* Sleep Mode
.
[194] Broken Belt
A Broken Belt condition has been
detected. This function must be enabled
in
22-60 Broken Belt Function
.
[196] Fire Mode
The frequency converter is operating in
Fire Mode. See parameter group
24-0*
Fire Mode
.
5-33 Term X30/7 Digi Out (MCB 101)
Option:
Function:
[0]
*
No
operation
This parameter is active when option module
MCB 101 is mounted in the frequency
converter. Same options and functions as
parameter group
5-3* Digital Outputs
.
5-34 On delay, Terminal 42 Digital Output
Range:
Function:
0.01 s
*
[0.00-600.00 s]
5-35 Off delay, Terminal 42 Digital Output
Range:
Function:
0.01 s
*
[0.00-600.00 s]
3.6.4 5-4* Relays
Parameters for configuring the timing and the output
functions for the relays.
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array
parameter.
Option:
Function:
[0]
No operation
Default for both relays
[1]
Control Ready
Control board receives supply voltage.
[2]
Drive ready
Frequency converter is ready for
operation and applies supply signal on
control board.
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
MG18B302 - Rev. 2013-09-02
43
3
3