4 Troubleshooting
4.1 Alarms and Warnings
A warning or an alarm is signalled by the relevant LED on
the front of the frequency converter and indicated by a
code on the display.
A warning remains active until its cause is no longer
present. Under certain circumstances operation of the
motor may still be continued. Warning messages may be
critical, but are not necessarily so.
In the event of an alarm, the frequency converter has
tripped. Alarms must be reset to restart operation once
their cause has been rectified.
This may be done in four ways:
1.
By pressing [Reset].
2.
Via a digital input with the “Reset” function.
3.
Via serial communication.
4.
By resetting automatically using the [Auto Reset]
function, which is a default setting for VLT HVAC
Basic Drive, see
NOTICE
After a manual reset pressing [Reset], press [Auto
On] or [Hand On] to restart the motor.
If an alarm cannot be reset, the reason may be that its
cause has not been rectified, or the alarm is trip-locked,
see
CAUTION
Alarms that are trip-locked offer additional protection,
means that the mains supply must be switched off
before the alarm can be reset. After being switched back
on, the frequency converter is no longer blocked and
may be reset as described above once the cause has
been rectified.
Alarms that are not trip-locked can also be reset using
the automatic reset function in
(Warning: automatic wake-up is possible!)
If a warning and alarm is marked against a code in the
table on the following page, this means that either a
warning occurs before an alarm, or it can be specified
whether it is a warning or an alarm that is to be
displayed for a given fault.
This is possible, for instance, in
. After an alarm or trip, the motor carries on
coasting, and the alarm and warning flash on the
frequency converter. Once the problem has been
rectified, only the alarm continues flashing.
No. Description
Warning
Alarm
Trip Lock
Parameter Reference
2
Live zero error
(X)
(X)
6-01
3
No motor
(X)
1-80
4
Mains phase loss
(X)
(X)
(X)
14-12
7
DC over voltage
X
X
8
DC under voltage
X
X
9
Inverter overloaded
X
X
10
Motor ETR over temperature
(X)
(X)
1-90
11
Motor thermistor over temperature
(X)
(X)
1-90
13
Over Current
X
X
X
14
Earth fault
X
X
X
16
Short Circuit
X
X
17
Control word timeout
(X)
(X)
8-04
24
Fan Fault (Only on 400V 30-90kW)
X
X
14-53
30
Motor phase U missing
(X)
(X)
4-58
31
Motor phase V missing
(X)
(X)
4-58
32
Motor phase W missing
(X)
(X)
4-58
38
Internal fault
X
X
44
Earth fault 2
X
X
47
Control Voltage Fault
X
X
48
VDD1 Supply Low
X
X
50
AMA Calibration Failed
X
Troubleshooting
VLT
®
HVAC Basic Drive FC 101 Programming Guide
MG18B302 - Rev. 2013-09-02
81
4
4
Summary of Contents for VLT HVAC Basic Drive FC 101
Page 2: ......
Page 104: ...www danfoss com drives MG18B302 130R0221 MG18B302 Rev 2013 09 02...