Parameter
Range
Default
Function
1-73 Flying Start
[0] Disabled
[1] Enabled
0
Select
[1] Enable
to enable the frequency
converter to catch a spinning motor. I.e. fan
applications. When PM is selected, Flying Start
is enabled.
-4999-4999
0
The minimum reference is the lowest value
obtainable by summing all references
-4999-4999
50
The maximum reference is the highest value
obtainable by summing all references
-100-100%
0
Enter the set point
0.05-3600.0 s
Size related
Ramp up time from 0 to rated
if Asynchron motor is selected;
ramp up time from 0 to
if PM motor is selected"
0.05-3600.0 s
Size related
Ramp down time from rated
to 0 if Asynchron motor is selected;
ramp down time from
to 0 if PM motor is selected
4-12 Motor Speed Low Limit [Hz]
0.0-400 Hz
0.0 Hz
Enter the minimum limit for low speed
4-14 Motor Speed High Limit [Hz]
0-400 Hz
65 Hz
Enter the minimum limit for high speed
0-400
Size related
Enter the maximum output frequency value
[0] Current
[1] Voltage
1
Select if terminal 54 is used for current- or
voltage input
0-10 V
0.07 V
Enter the voltage that corresponds to the low
reference value
0-10 V
10 V
Enter the voltage that corresponds to the low
high reference value
0-20 mA
4
Enter the current that corresponds to the high
reference value
0-20 mA
20
Enter the current that corresponds to the high
reference value
6-24 Terminal 54 Low Ref./Feedb.
Value
-4999-4999
0
Enter the feedback value that corresponds to
the voltage or current set in
6-25 Terminal 54 High Ref./Feedb.
Value
-4999-4999
50
Enter the feedback value that corresponds to
the voltage or current set in
/
6-26 Terminal 54 Filter Time
Constant
0-10 s
0.01
Enter the filter time comstant
20-81 PI Normal/ Inverse Control
[0] Normal
[1] Inverse
0
Select
[0] Normal
to set the process control to
increase the output speed when the process
error is positive. Select
[1] Inverse
to reduce
the output speed.
0-200 Hz
0
Enter the motor speed to be attained as a
start signal for commencement of PI control
0-10
0.01
Enter the process controller proportional gain.
Quick control is obtained at high amplifi-
cation. However if amplification is too great,
the process may become unstable
0.1-999.0 s
999.0 s
Enter the process controller integral time.
Obtain quick control through a short integral
time, though if the integral time is too short,
the process becomes unstable. An excessively
long integral time disables the integral action.
Table 2.5 Closed Loop Application
How to Programme
VLT
®
HVAC Basic Drive FC 101 Programming Guide
16
MG18B302 - Rev. 2013-09-02