14-20 Reset Mode
Option:
Function:
[3]
Automatic reset x 3
[4]
Automatic reset x 4
[5]
Automatic reset x 5
[6]
Automatic reset x 6
[7]
Automatic reset x 7
[8]
Automatic reset x 8
[9]
Automatic reset x 9
[10] Automatic reset x 10
[11] Automatic reset x 15
[12] Automatic reset x 20
[13] Infinite auto reset
Select
[13] Infinite Automatic Reset
for
continuous resetting after tripping.
14-21 Automatic Restart Time
Range:
Function:
10 s
*
[0 - 600
s]
Enter the time interval from trip to start of the
automatic reset function. This parameter is
active when
is set to
[1] - [13]
Automatic reset
.
14-22 Operation Mode
Option:
Function:
Select
[2] Initialisation
to reset all parameter
values to default.
[0]
*
Normal
operation
Select
[0] Normal operation
for normal
operation of the frequency converter with the
motor in the selected application.
[2]
Initiali-
sation
Select
[2] Initialisation
to reset all parameter
values to default settings, except for
,
and
. The frequency converter is
reset during the next power-up.
also reverts to the
default setting
[0] Normal operation
.
14-23 Typecode Setting
Range:
Function:
0
*
[0 - 255 ] Typecode re-writing. Use this parameter to set
the typecode matching the specific frequency
converter.
14-27 Action At Inverter Fault
Option:
Function:
Select how the frequency converter should react
at inverter fault. Action At Inverter Fault
[0]
Trip
[1]
*
Warning
14-28 Production Settings
Option:
Function:
[0]
*
No action
Production use only.
14-28 Production Settings
Option:
Function:
[1]
Service reset
[3]
Software Reset
14-29 Service Code
Range:
Function:
0
*
[0 - 0x7FFFFFFF ]
Service use only.
3.10.4 14-4* Energy Optimising
Parameters for adjusting the energy optimisation level in
both Variable Torque (VT) and Automatic Energy Optimi-
sation (AEO) mode.
Automatic Energy Optimisation is only active if
, is set for
[3] Auto Energy Optim
.
14-40 VT Level
Range:
Function:
90 %
*
[40 - 90 %]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the level of motor magnetisation at
low speed. Selection of a low value reduces
energy loss in the motor, but also reduces
load capability.
90%
*
[40-90%]
14-41 AEO Minimum Magnetisation
Range:
Function:
66 %
*
[40 - 75 %] Enter the minimum allowable magnetisation
for AEO. Selection of a low value reduces
energy loss in the motor, but can also
reduce resistance to sudden load changes.
66%
*
[40-75%]
3.10.5 14-5* Environment
These parameters help the frequency converter to operate
under special environmental conditions.
14-50 RFI Filter
Option: Function:
[0]
Off Select
[0] Off
only if the frequency converter is fed by
an isolated mains source (IT mains).
In this mode, the internal RFI filter capacitors between
chassis and the mains RFI filter circuit are cut-out to
reduce the ground capacity currents.
[1]
*
On Select
[1] On
to ensure that the frequency converter
complies with EMC standards.
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
66
MG18B302 - Rev. 2013-09-02
3
3