[6]
Running / no
warning
The output speed is higher than the
speed set in
1-81 Min Speed for Function
at Stop [RPM]
. The motor is running and
there are no warnings.
[8]
Run on
reference / no
warning
The motor runs at reference speed.
[9]
Alarm
An alarm activates the output. There are
no warnings.
[10]
Alarm or
warning
An alarm or a warning activates the
output.
[11]
At torque limit
The torque limit set in
4-16 Torque Limit
Motor Mode
or
4-13 Motor Speed High
Limit [RPM]
has been exceeded.
[12]
Out of current
range
The motor current is outside the range
set in
4-18 Current Limit
.
[13]
Below current,
low
The motor current is lower than set in
4-50 Warning Current Low
.
[14]
Above current,
high
The motor current is higher than set in
4-51 Warning Current High
.
[16]
Below speed,
low
The output speed is lower than the
setting in
4-52 Warning Speed Low
.
[17]
Above speed,
high
The output speed is higher than the
setting in
4-53 Warning Speed High
.
[18]
Out of feedback
range
The feedback is outside the range set in
4-56 Warning Feedback Low
and
4-57 Warning Feedback High
.
[19]
Below feedback
low
The feedback is below the limit set in
4-56 Warning Feedback Low
.
[20]
Above feedback
high
The feedback is above the limit set in
4-57 Warning Feedback High
.
[21]
Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the
brake resistor, or the thermistor.
[25]
Reverse
Reversing. Logic ‘1’ =
relay activated, 24V
DC when CW rotation of the motor.
Logic ‘0’ = relay not activated, no signal,
when CCW rotation of the motor.
[26]
Bus OK
Active communication (no time-out) via
the serial communication port.
[27]
Torque limit
and stop
Use in performing a coasting stop and in
torque limit condition. If the frequency
converter has received a stop signal and
is at the torque limit, the signal is Logic
‘0’.
[28]
Brake, no
warning
The brake is active and there are no
warnings.
[29]
Brake ready, no
fault
The brake is ready for operation and
there are no faults.
[30]
Brake fault
(IGBT)
The output is Logic ‘1’ when the brake
IGBT is short-circuited. Use this function
to protect the frequency converter if
there is a fault on the brake modules.
Use the output/relay to cut out the main
voltage from the frequency converter.
[35]
External
Interlock
External Interlock function has been
activated via one of the digital inputs.
[40]
Out of ref range
[41]
Below reference
low
[42]
Above reference
high
[45]
Bus Ctrl
[46]
Bus Ctrl 1 if
timeout
[47]
Bus Ctrl 0 if
timeout
[60]
Comparator 0
See parameter group
13-1* Comparators
.
If Comparator 0 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
[61]
Comparator 1
See parameter group
13-1* Comparators
.
If Comparator 2 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
[62]
Comparator 2
See parameter group
13-1* Comparators
.
If Comparator 2 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
[63]
Comparator 3
See parameter group
13-1* Comparators
.
If Comparator 3 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
[64]
Comparator 4
See parameter group
13-1* Comparators
.
If Comparator 4 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
[65]
Comparator 5
See parameter group
13-1* Comparators
.
If Comparator 5 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
[70]
Logic Rule 0
See parameter group
13-4* Logid Rules
. If
Logic Rule 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[71]
Logic Rule 1
See parameter group
13-4* Logid Rules
. If
Logic Rule 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[72]
Logic Rule 2
See parameter group
13-4* Logid Rules
. If
Logic Rule 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[73]
Logic Rule 3
See parameter group
13-4* Logid Rules
. If
Logic Rule 3 is evaluated as TRUE, the
output is high. Otherwise, it is low.
[74]
Logic Rule 4
See parameter group
13-4* Logid Rules
. If
Logic Rule 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[75]
Logic Rule 5
See parameter group
13-4* Logid Rules
. If
Logic Rule 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
42
MG18B302 - Rev. 2013-09-02
3
3
Summary of Contents for VLT HVAC Basic Drive FC 101
Page 2: ......
Page 104: ...www danfoss com drives MG18B302 130R0221 MG18B302 Rev 2013 09 02...