6-94 Terminal 42 Output Max Scale
Range:
Function:
100
%
*
[0 -
200
%]
Scale for the maximum output (20 mA) of the
scaling at Terminal 42. Set the value to be the
percentage of the full range of the variable
selected in
6-91 Terminal 42 Analog Output
.
(mA)
0%
20
0/4
100%
Current
Analogue
output
Min Scale
par. 6-93
Variable
for
output
example:
Power
Analogue
Output
Max Scale
par. 6-94
Illustration 3.12 Output Max Scale
6-96 Terminal 42 Output Bus Control
Range:
Function:
0
*
[0 - 16384 ]
6-98 Drive Type
Range:
Function:
0
*
[0 - 0 ]
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
52
MG18B302 - Rev. 2013-09-02