13-11 Comparator Operator
Array [6]
Option:
Function:
[1]
*
Approx.Equal
(~)
Select
[1] ≈
for the result of the evaluation
to be TRUE, when the variable selected in
is approxi-
mately equal to the fixed value in
[2]
Greater Than
(>)
Select
[2] >
for the inverse logic of option
[0] <
.
13-12 Comparator Value
Array [6]
Range:
Function:
0
*
[-9999 -
9999 ]
Enter the ‘trigger level’ for the variable that is
monitored by this comparator. This is an array
parameter containing comparator values 0 to 5.
3.9.4 13-2* Timers
Use the result (TRUE or FALSE) from
timers
directly to
define an
event
(see
), or as
boolean input in a
logic rule
(see
or
).
A timer is only FALSE when started by an action (i.e.
[29]
Start timer 1
) until the timer value entered in this
parameter is elapsed. Then it becomes TRUE again.
All parameters in this parameter group are array
parameters with index 0 to 2. Select index 0 to program
Timer 0, select index 1 to program Timer 1, and so on.
13-20 SL Controller Timer
Array [8]
Range:
Function:
0 s
*
[0 -
3600 s]
Enter the value to define the duration of the
FALSE output from the programmed timer. A
timer is only FALSE if it is started by an action
(see
13-52 SL Controller Action
[29-31] and
13-52 SL
Controller Action
[70-74] Start timer X) and until
the timer value has elapsed. Array parameter
containing timers 0 to 7.
3.9.5 13-4* Logic Rules
Combine up to 3 boolean inputs (TRUE/FALSE inputs) from
timers, comparators, digital inputs, status bits and events
using the logical operators AND, OR, and NOT. Select
boolean inputs for the calculation in
,
and
. Define the operators used to logically combine
the selected inputs in
and
. . .
. . .
. . .
. . .
Par. 13-43
Logic Rule Operator 2
Par. 13-41
Logic Rule Operator 1
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Par. 13-44
Logic Rule Boolean 3
130BB673.10
Illustration 3.15 Logic Rules
Priority of calculation
The results of
and
are calculated
first. The outcome (TRUE/FALSE) of this calculation is
combined with the settings of
and
, yielding the final result
(TRUE/FALSE) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[0]
*
False
Enters the fixed value of FALSE in the
logic rule.
[1]
True
Enters the fixed value TRUE in the logic
rule.
[2]
Running
See
for further
description.
[3]
In range
See
for further
description.
[4]
On reference
See
for further
description.
[7]
Out of current
range
See
for further
description.
[8]
Below I low
See
for further
description.
[9]
Above I high
See
for further
description.
[16] Thermal warning
See
for further
description.
[17] Mains out of
range
See
for further
description.
[18] Reversing
See
for further
description.
[19] Warning
See
for further
description.
[20] Alarm (trip)
See
for further
description.
[21] Alarm (trip lock)
See
for further
description.
[22] Comparator 0
Use the result of comparator 0 in the
logic rule.
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
60
MG18B302 - Rev. 2013-09-02
3
3
Summary of Contents for VLT HVAC Basic Drive FC 101
Page 2: ......
Page 104: ...www danfoss com drives MG18B302 130R0221 MG18B302 Rev 2013 09 02...