5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array
parameter.
Option:
Function:
[72]
Logic rule 2
See parameter group
13-4* Logic Rules
. If
Logic Rule 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[73]
Logic rule 3
See parameter group
13-4* Logic Rules
. If
Logic Rule 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[74]
Logic rule 4
See parameter group
13-4* Logic Rules
. If
Logic Rule 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[75]
Logic rule 5
See parameter group
13-4* Logic Rules
. If
Logic Rule 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[80]
SL digital output
A
See
. The input
goes high whenever the Smart Logic
Action
[38] Set dig. out. A high
is
executed. The input goes low whenever
the Smart Logic
[32] Action Set dig. out.
A low is executed.
[81]
SL digital output
B
See
. The input
goes high whenever the Smart Logic
Action
[39] Set dig. out. Bhigh
is
executed. The input goes low whenever
the Smart Logic
[33] Action Set dig. out. B
low
is executed.
[82]
SL digital output
C
See
. The input
goes high whenever the Smart Logic
Action
[40] Set dig. out. C high
is
executed. The input goes low whenever
the Smart Logic
[34] Action Set dig. out. C
low
is executed.
[83]
SL digital output
D
See
. The input
goes high whenever the Smart Logic
[41] Action Set dig. out. D
high is
executed. The input goes low whenever
the Smart Logic
[35] Action Set dig. out.
D low
is executed.
[160] No alarm
The output is high when no alarm is
present.
[161] Running reverse The output is high when the frequency
converter is running counter clockwise
(the logical product of the status bits
‘running’ AND ‘reverse’).
[165] Local ref. active
The output is high when
3-13 Reference
Site
=
[2] Local
or when
3-13 Reference
Site
=
[0] Linked to hand auto
at the
same time as the LCP is in [Hand on]
mode.
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array
parameter.
Option:
Function:
[166] Remote ref.
active
The output is high when
3-13 Reference
Site
[1] or Linked to hand/auto [0]
while
the LCP is in [Auto on] mode.
[167] Start command
activ
The output is high when there is an
active Start command (i.e. via digital
input bus connection or [Hand on] or
[Auto on], and no Stop command is
active.
[168] Drive in hand
mode
The output is high when the frequency
converter is in Hand on mode (as
indicated by the LED light above [Hand
on].
[169] Drive in auto
mode
The output is high when the frequency
converter is in Hand on mode (as
indicated by the LED light above [Auto
on].
[193] Sleep Mode
The frequency converter/system has
turned into sleep mode. See parameter
group
22-4* Sleep Mode
.
[194] Broken Belt
Function
A Broken Belt condition has been
detected. This function must be enabled
in
.
[196] Fire Mode
The frequency converter is operating in
Fire Mode. See parameter group
24-0*
Fire Mode
.
[198] Drive Bypass
To be used as signal for activating an
external electromechanical bypass
switching the motor direct on line.
See parameter group
24-1* Drive Bypass.
5-41 On Delay, Relay
Array [9], (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5
[4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Range:
Function:
0.01 s
*
[0.01 -
600 s]
Enter the delay of the relay cut-in time. The
relay only cuts in if the condition in
5-40 Function Relay
is uninterrupted during the
specified time. Select one of available
mechanical relays and Relay Option MCB 105 in
an array function. See
5-40 Function Relay
. Relay
3-6 are included in Extended Relay Card MCB
113.
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
MG18B302 - Rev. 2013-09-02
45