5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array
parameter.
Option:
Function:
[3]
Drive ready/
remote control
Frequency converter is ready for
operation in Auto On-mode.
[4]
Standby / no
warning
Frequency converter is ready for
operation. No start or stop command is
given. No warnings are present.
[5]
Drive running
Motor is running.
[6]
Running / no
warning
Motor runs, and no warning are present.
[7]
Run in range/no
warning
Motor runs within programmed current
ranges, see
and
. No
warnings are present.
[8]
Run on ref/no
warning
Motor runs at reference speed and with
no warnings.
[9]
Alarm
An alarm activates output.
[10]
Alarm or
warning
An alarm or warning activates output.
[12]
Out of current
range
Motor current is outside range set in
and
.
[13]
Below current,
low
Motor current is lower than set in
.
[14]
Above current,
high
Motor current is higher than set in
.
[16]
Below speed,
low
[17]
Above speed,
high
[19]
Below feedback,
low
[20]
Above feedback,
high
[21]
Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in motor,
frequency converter or thermistor.
[22]
Ready, no
thermal warning
Frequency converter is ready for
operation and no over-temperature
warning is present.
[23]
Remote, ready,
no thermal
warning
Frequency converter is ready for
operation in Auto mode, and no over-
temperature warning is present.
[24]
Ready, Voltage
OK
Frequency converter is ready for
operation and mains voltage is within
specified voltage range.
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array
parameter.
Option:
Function:
[25]
Reverse
Motor runs/is ready to run clockwise
when logic = 0 and counter clockwise
when logic = 1. Output changes as soon
as reversing signal is applied.
[26]
Bus OK
Active communication (no time-out) via
serial communication port.
[35]
External
Interlock
See digital input.
[36]
Control word bit
11
Bit 11 in control word controls relay.
[37]
Control word bit
12
Bit 12 in control word controls relay.
[41]
Below reference,
low
[42]
Above ref, high
[45]
Bus Control
[60]
Comparator 0
See parameter group
13-1* Comparators
.
If Comparator 0 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
[61]
Comparator 1
See parameter group
13-1* Comparators
.
If Comparator 2 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
[62]
Comparator 2
See parameter group
13-1* Comparators
.
If Comparator 2 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
[63]
Comparator 3
See parameter group
13-1* Comparators
.
If Comparator 3 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
[64]
Comparator 4
See parameter group
13-1* Comparators
.
If Comparator 4 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
[65]
Comparator 5
See parameter group
13-1* Comparators
.
If Comparator 5 is evaluated as TRUE,
the output goes high. Otherwise, it is
low.
[70]
Logic rule 0
See parameter group
13-4* Logic Rules
. If
Logic Rule 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[71]
Logic rule 1
See parameter group
13-4* Logic Rules
. If
Logic Rule 1 is evaluated as TRUE, the
output goes high. Otherwise, it islow.
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
44
MG18B302 - Rev. 2013-09-02
3
3