13-01 Start Event
Option:
Function:
[27]
Logic rule 1
Use the result of logic rule 1 in the
logic rule.
[28]
Logic rule 2
Use the result of logic rule 2 in the
logic rule.
[29]
Logic rule 3
Use the result of logic rule 3 in the
logic rule.
[33]
Digital input
DI18
Use the value of DI18 in the logic rule
(High = TRUE).
[34]
Digital input
DI19
Use the value of DI19 in the logic rule
(High = TRUE).
[35]
Digital input
DI27
Use the value of DI27 in the logic rule
(High = TRUE).
[36]
Digital input
DI29
Use the value of DI29 in the logic rule
(High = TRUE).
[39]
*
Start command
This event is TRUE if the frequency
converter is started (either via digital
input, field bus or other).
[40]
Drive stopped
This event is TRUE if the frequency
converter is stopped or coasted (either
via digital input, fieldbus or other).
[42]
Auto Reset Trip
This event is TRUE if the frequency
converter is tripped (but not trip-
locked) and an Automatic Reset is
issued.
[50]
Comparator 4
Use the result of comparator 4 in the
logic rule.
[51]
Comparator 5
Use the result of comparator 5 in the
logic rule.
[60]
Logic rule 4
Use the result of logic rule 4 in the
logic rule.
[61]
Logic rule 5
Use the result of logic rule 5 in the
logic rule.
[83]
Broken Belt
A broken belt condition has been
detected. This function must be
enabled in
.
13-02 Stop Event
Option:
Function:
Select the condition (TRUE or FALSE)
which deactivates the Smart Logic
Controller.
[0]
False
Enters the fixed value of FALSE in the
logic rule.
[1]
True
Enters the fixed value TRUE in the
logic rule.
[2]
Running
See
for further
description.
13-02 Stop Event
Option:
Function:
[3]
In range
See
for further
description.
[4]
On reference
See
for further
description.
[7]
Out of current
range
See
for further
description.
[8]
Below I low
See
for further
description.
[9]
Above I high
See
for further
description.
[16]
Thermal warning
See
for further
description.
[17]
Mains out of
range
See
for further
description.
[18]
Reversing
See
for further
description.
[19]
Warning
See
for further
description.
[20]
Alarm (trip)
See
for further
description.
[21]
Alarm (trip lock)
See
for further
description.
[22]
Comparator 0
Use the result of comparator 0 in the
logic rule.
[23]
Comparator 1
Use the result of comparator 1 in the
logic rule.
[24]
Comparator 2
Use the result of comparator 2 in the
logic rule.
[25]
Comparator 3
Use the result of comparator 3 in the
logic rule.
[26]
Logic rule 0
Use the result of logic rule 0 in the
logic rule.
[27]
Logic rule 1
Use the result of logic rule 1 in the
logic rule.
[28]
Logic rule 2
Use the result of logic rule 2 in the
logic rule.
[29]
Logic rule 3
Use the result of logic rule 3 in the
logic rule.
[30]
SL Time-out 0
Use the result of timer 0 in the logic
rule.
[31]
SL Time-out 1
Use the result of timer 1 in the logic
rule.
[32]
SL Time-out 2
Use the result of timer 2 in the logic
rule.
[33]
Digital input DI18 Use the value of DI18 in the logic rule
(High = TRUE).
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
58
MG18B302 - Rev. 2013-09-02
3
3