14-51 DC-Link Voltage Compensation
Option:
Function:
[0]
Off
Disables DC Link Compensation.
[1]
*
On
Enables DC Link Compensation.
14-52 Fan Control
Option:
Function:
Only valid for the following frequency
converters: 380-480 V, 30-90 kW.
[0]
*
Auto
[4]
Auto Low Temp
Env.
14-53 Fan Monitor
Option:
Function:
Select which reaction the frequency converter
should take in case a fan fault is detected. (Only
valid for some frequency converter sizes.)
[0]
Disabled
[1]
*
Warning
[2]
Trip
14-55 Output Filter
Option:
Function:
Select whether an output
filter is present.
[0]
*
No Filter
[1]
Sine-Wave Filter
[3]
Sine-Wave Filter with
Feedback
14-63 Min Switch Frequency
Set the minimum switch frequency allowed by the output filter.
Option:
Function:
[2]
*
2.0 kHz
[3]
3.0 kHz
[4]
4.0 kHz
[5]
5.0 kHz
[6]
6.0 kHz
[7]
8.0 kHz
[8]
10.0 kHz
[9]
12.0kHz
[10]
16.0kHz
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
MG18B302 - Rev. 2013-09-02
67