Page
69
of 77
SK2019 FCSD(H)-V/P-ECM-001
LED Display and Error Description
Flexible Control PCB - W Control Type
Fan speed setting
LED Display
Condition
High speed
Red LED On
Normal
Medium speed
Yellow LED On
Normal
Low speed
Green LED On
Normal
For all units - Green LED blinks
Item
Blink
Reason
Remedy
Indoor coil sensor 1 failure
Green LED blinks 4 times,
stops for 3s
Ti1 sensor connection is
not good or damaged.
1.
Check if Ti1 plug is
connected or not.
2.
Check sensor’s resistor is
good or not.
Water pump failure
Green LED blinks 7 times,
stops for 3s
Float switch is opened.
1.
Check if the condensate
water pipe is connected or
not.
2.
Check if the pump is
functioning or not.
EC motor failure
Green LED blinks 9 times,
stops for 3s
No EC motor feedback
1.
Check DIPB-SW5 and SW6
setting.
2.
Check the EC motor
Anti-frozen protection
Green LED blinks11 times,
stops for 3s
When unit is standby,
Ti1<2ºC.
1. Turn on unit to keep Ti
higher than 5ºC
Summary of Contents for FDLA-09
Page 1: ...SK2018 GLOBAL FDLA V P AC 001 FDLA V P AC MOTOR...
Page 27: ...Page 26 of 51 SK2018 GLOBAL FDLA V P AC 001 Configuration Settings...
Page 53: ...FDHD V P AC MOTOR...
Page 69: ...B 1 4 4 Electrical connections T Configuration standard version...
Page 74: ...Wiring Diagram D 2 SK NCPDWH 001b S Configuration Full Control PCB...
Page 76: ...Configuration Settings D 3...
Page 111: ......
Page 112: ...SK2019 FCSD H V P ECM 001 FCSD H V P ECM MOTOR...
Page 190: ...SK2019 FCSD H V P ECM 001...
Page 191: ...Page 1 of 59 SK2015 FMCD V EC 001 FMCD ECM MOTOR...
Page 210: ...Page 20 of 59 SK2015 SWC V EC 001 D 1 3 Wiring Diagram SK NCSWC 001...
Page 233: ...Page 43 of 59 SK2015 SWC V EC 001 D 4 2 Wiring diagram SK NCSWC 002...
Page 248: ...Page 58 of 59 SK2015 SWC V EC 001 Troubleshooting Guide E 4...
Page 249: ...Page 59 of 59 SK2015 SWC V EC 001...
Page 250: ...FSTD C V P ECM MOTOR...
Page 256: ...Page 7 of 73 SK2015 FSTDC V P ECM 001 A 2 Unit Appearance FSTDC VAR FSTDC HAR FSTD...