SK2019 FCSD(H)-V/P-ECM-001
Control Logic For 4-Pipe System
Note: 4-pipe system must always be equipped with 2 valves.
COOL MODE
a)
MTV2, AUX1 and Electrical Heater are always off.
b)
If Tr ≥ Ts + 1ºC (or + 4ºC if economy contact is activated), then cool operation is activated, MTV1 and AUX2 are turned on.
Indoor fan runs at set speed.
c)
If Tr < Ts, then cool operation is terminated, MTV1 and AUX2 are turned off. Indoor fan runs at set speed.
d)
The range of Ts is 16 - 30ºC
e)
Indoor fan speed can be adjusted to low, medium, high and auto.
f)
When turned on, MTV1 requires 30 seconds before it is fully open.
g)
When turned off, MTV1 requires 120 seconds before it is fully closed.
h)
When the unit is turned off, the indoor fan will shut down after 5 seconds.
LOW TEMPERATURE PROTECTION OF INDOOR COIL
a)
If Ti1 ≤ 2ºC for 2 minutes, then MTV1 and AUX2 are turned off. If indoor fan is set for low speed, then it will run at
medium speed. If it is set at medium or high speed, then it will keep running at the same speed.
b)
If Ti1 ≥ 5ºC for 2 minutes, then MTV1 and AUX2 are turned on. Indoor fan runs at set speed.
FAN MODE
a)
Indoor fan runs at the set speed while heater, MTV1, MTV2, AUX1 and AUX2 are turned off.
b)
Indoor fan speed can be adjusted to low, medium and high.
HEAT MODE
Without Electrical Heater
a)
MTV1, AUX2 and are heater always off.
b)
If Tr ≤ Ts - 1ºC (or - 4ºC if economy contact is activated), then heat operation is activated, MTV2 and AUX1 are turned on.
Indoor fan runs at the set speed.
c)
If Tr > Ts, then heat operation is terminated, MTV2 and AUX1 are turned off. Indoor fan runs at Modbus 310000 setting.
d)
The range of Ts is 16 - 30ºC.
e)
Indoor fan speed can be adjusted to low, medium, high and auto.
f)
When turned on, MTV2 requires 30 seconds before it is fully open.
g)
When turned off, MTV2 requires 120 seconds before it is fully closed.
With Electrical Heater as Booster
a)
MTV1 and AUX2 are always off.
b)
If Tr ≤ Ts - 1ºC (or - 4ºC if economy contact is activated), then heat operation is activated, MTV2 and AUX1 are turned on.
Indoor fan runs at the set speed.
c)
If Tr > Ts, then heat operation is terminated, MTV2 and AUX1 are turned off. Indoor fan runs at Modbus 310000 setting.
d)
If Ti2 < 40ºC, then the electrical heater is turned on. If 40ºC ≤ Ti2 < 45ºC, then the electrical heater maintains its original
state. If Ti2 ≥ 45ºC, then the electrical heater is turned off.
e)
The range of Ts is 16 - 30ºC
f)
Indoor fan speed can be adjusted to low, medium, high and auto.
g)
When turned on, MTV2 requires 30 seconds before it is fully open.
h)
When turned off, MTV2 requires 120 seconds before it is full closed.
Summary of Contents for FDLA-09
Page 1: ...SK2018 GLOBAL FDLA V P AC 001 FDLA V P AC MOTOR...
Page 27: ...Page 26 of 51 SK2018 GLOBAL FDLA V P AC 001 Configuration Settings...
Page 53: ...FDHD V P AC MOTOR...
Page 69: ...B 1 4 4 Electrical connections T Configuration standard version...
Page 74: ...Wiring Diagram D 2 SK NCPDWH 001b S Configuration Full Control PCB...
Page 76: ...Configuration Settings D 3...
Page 111: ......
Page 112: ...SK2019 FCSD H V P ECM 001 FCSD H V P ECM MOTOR...
Page 190: ...SK2019 FCSD H V P ECM 001...
Page 191: ...Page 1 of 59 SK2015 FMCD V EC 001 FMCD ECM MOTOR...
Page 210: ...Page 20 of 59 SK2015 SWC V EC 001 D 1 3 Wiring Diagram SK NCSWC 001...
Page 233: ...Page 43 of 59 SK2015 SWC V EC 001 D 4 2 Wiring diagram SK NCSWC 002...
Page 248: ...Page 58 of 59 SK2015 SWC V EC 001 Troubleshooting Guide E 4...
Page 249: ...Page 59 of 59 SK2015 SWC V EC 001...
Page 250: ...FSTD C V P ECM MOTOR...
Page 256: ...Page 7 of 73 SK2015 FSTDC V P ECM 001 A 2 Unit Appearance FSTDC VAR FSTDC HAR FSTD...