Heat
mode
with
electrical
heater
as
primary
heat
source
a)
MTV1,
MTV2,
and
AUX2
are
always
off
b)
If
Ti2
≤
30ºC
(or
Ti2
is
damaged
or
disconnected),
AND
if
Tr
≤
Ts
‐
1ºC
(or
‐
4ºC
if
economy
contact
is
activated),
heat
operation
is
activated,
electrical
heater
and
AUX1
are
turned
on.
Indoor
fan
runs
at
set
speed.
c)
If
Tr
>
Ts,
then
heat
operation
is
terminated
and
the
electrical
heater
and
AUX1
are
turned
off.
Indoor
fan
repeatedly
runs
at
low
fan
speed
for
30
seconds
and
then
stops
for
3
minutes.
d)
The
range
of
Ts
is
16
‐
30
ºC
e)
Indoor
fan
speed
can
be
adjusted
to
low,
medium,
high
and
auto.
PRE
‐
HEAT
Pre
‐
heat
without
electrical
heater
a)
If
Ti1
<
36ºC
[or
<
28ºC
is
selected
by
DIPB
‐
S2
position
SW4],
then
MTV1
and
AUX1
are
turned
on,
indoor
fan
remains
off.
b)
If
Ti1
≥
38ºC
[or
≥
30ºC
is
selected
by
DIPB
‐
S2
position
SW4],
then
MTV1
and
AUX1
are
turned
on,
indoor
fan
runs
at
set
speed.
c)
If
the
indoor
coil
temperature
sensor
is
damaged,
then
the
pre
‐
heat
time
is
set
for
2
minutes.
Indoor
fan
runs
at
set
speed.
Pre
‐
heat
with
electrical
heater
Indoor
fan
will
turn
on
after
the
electrical
heater
has
been
turned
on
for
10
seconds.
POST
‐
HEAT
Post
‐
heat
without
electrical
heater
a)
If
Ti1
≥
38ºC,
then
MTV1
and
AUX
1
are
off,
then
indoor
fan
continues
to
run
at
set
speed.
b)
If
36ºC
≤
Ti1
≤
38ºC,
then
MTV1
and
AUX1
are
turned
off.
Then
indoor
fan
maintains
its
original
state.
c)
If
Ti1
<
36ºC,
then
MTV1
and
AUX1
are
turned
off.
Then
indoor
fan
repeatedly
runs
for
30
seconds
and
then
stops
for
3
minutes.
d)
If
the
indoor
coil
temperature
sensor
is
damaged,
then
the
post
‐
heat
time
is
set
for
3
minutes.
Indoor
fan
runs
at
set
speed.
Post
‐
heat
with
electrical
heater
Indoor
fan
will
shut
down
after
the
unit
has
been
turned
off
for
20
seconds.
OVER
‐
HEAT
PROTECTION
OF
INDOOR
COIL
a)
If
Ti1
≥
75ºC,
then
MTV1
and
AUX1
are
turned
off.
Indoor
fan
remains
on
and
runs
at
high
speed.
b)
If
Ti1
<
70ºC,
then
MTV1
and
AUX1
are
turned
on.
Indoor
fan
remains
on
and
runs
at
set
speed.
c)
If
the
indoor
coil
temperature
sensor
is
damaged,
then
the
protection
mode
will
be
overridden
and
the
unit
will
work
according
to
the
pre
‐
heat
and
post
‐
heat
program.
DEHUMIDIFICATION
MODE
a)
MTV2,
AUX1
and
heater
are
always
off.
b)
If
Tr
≥
25ºC,
then
MTV1
and
AUX2
will
be
ON
for
3
minutes,
and
then
OFF
for
4
minutes.
c)
If
16ºC
≤
Tr
<
25ºC,
then
MTV1
and
AUX2
will
be
ON
for
3
minutes,
and
then
OFF
for
6
minutes.
d)
If
Tr
<
16ºC,
then
MTV1
and
AUX2
will
be
turned
off
for
4
minutes.
e)
At
the
end
of
the
above
dehumidification
cycle,
the
system
will
decide
the
next
dehumidification
control
option.
Indoor
fan
will
run
at
low
speed
throughout
the
dehumidification
process.
Summary of Contents for FDLA-09
Page 1: ...SK2018 GLOBAL FDLA V P AC 001 FDLA V P AC MOTOR...
Page 27: ...Page 26 of 51 SK2018 GLOBAL FDLA V P AC 001 Configuration Settings...
Page 53: ...FDHD V P AC MOTOR...
Page 69: ...B 1 4 4 Electrical connections T Configuration standard version...
Page 74: ...Wiring Diagram D 2 SK NCPDWH 001b S Configuration Full Control PCB...
Page 76: ...Configuration Settings D 3...
Page 111: ......
Page 112: ...SK2019 FCSD H V P ECM 001 FCSD H V P ECM MOTOR...
Page 190: ...SK2019 FCSD H V P ECM 001...
Page 191: ...Page 1 of 59 SK2015 FMCD V EC 001 FMCD ECM MOTOR...
Page 210: ...Page 20 of 59 SK2015 SWC V EC 001 D 1 3 Wiring Diagram SK NCSWC 001...
Page 233: ...Page 43 of 59 SK2015 SWC V EC 001 D 4 2 Wiring diagram SK NCSWC 002...
Page 248: ...Page 58 of 59 SK2015 SWC V EC 001 Troubleshooting Guide E 4...
Page 249: ...Page 59 of 59 SK2015 SWC V EC 001...
Page 250: ...FSTD C V P ECM MOTOR...
Page 256: ...Page 7 of 73 SK2015 FSTDC V P ECM 001 A 2 Unit Appearance FSTDC VAR FSTDC HAR FSTD...