D.1.6.
Control
Logics
For
4
‐
Pipe
System
Note:
unit
equipped
with
4x2
switching
device.
COOL
MODE
a)
MTV2,
AUX1
and
Electrical
Heater
are
always
off.
b)
If
Tr
≥
Ts
+
1ºC
(or
+
4ºC
if
economy
contact
is
activated),
then
cool
operation
is
activated,
MTV1
and
AUX2
are
turned
on.
Indoor
fan
runs
at
set
speed.
c)
If
Tr
<
Ts,
then
cool
operation
is
terminated,
MTV1
and
AUX2
are
turned
off.
Indoor
fan
runs
at
set
speed.
d)
The
range
of
Ts
is
16
‐
30ºC
e)
Indoor
fan
speed
can
be
adjusted
to
low,
medium,
high
and
auto.
f)
When
turned
on,
MTV1
requires
30
seconds
before
it
is
fully
open.
g)
When
turned
off,
MTV1
requires
120
seconds
before
it
is
fully
closed.
h)
When
the
unit
is
turned
off,
the
indoor
fan
will
shut
down
after
5
seconds.
FAN
MODE
a)
Indoor
fan
runs
at
the
set
speed
while
heater,
MTV1,
MTV2,
AUX1
and
AUX2
are
turned
off.
b)
Indoor
fan
speed
can
be
adjusted
to
low,
medium
and
high.
HEAT
MODE
Without
Electrical
Heater
a)
MTV1,
AUX2
and
electric
heater
are
always
off.
b)
If
Tr
≤
Ts
‐
1ºC
(or
‐
4ºC
if
economy
contact
is
activated),
then
heat
operation
is
activated
and
MTV2
and
AUX1
are
turned
on.
Indoor
fan
runs
at
the
set
speed.
c)
If
Tr
>
Ts,
then
heat
operation
is
terminated
and
MTV2
and
AUX1
are
turned
off.
Indoor
fan
runs
at
200RPM.
d)
The
range
of
Ts
is
16
‐
30ºC.
e)
Indoor
fan
speed
can
be
adjusted
to
low,
medium,
high
and
auto.
f)
When
turned
on,
MTV2
requires
30
seconds
before
it
is
fully
open.
g)
When
turned
off,
MTV2
requires120
seconds
before
it
is
fully
closed.
With
Electrical
Heater
as
Booster
a)
MTV1
and
AUX2
are
always
off.
b)
If
Tr
≤
Ts
‐
1ºC
(or
–
4ºC
if
economy
contact
is
activated),
then
heat
operation
is
activated
and
MTV2
and
AUX1
are
turned
on.
Indoor
fan
runs
at
the
set
speed.
c)
If
Tr
>
Ts,
then
heat
operation
is
terminated
and
MTV2
and
AUX1
are
turned
off.
Indoor
fan
runs
at
200RPM.
d)
If
Ti1
<
40ºC,
then
the
electrical
heater
is
turned
on.
If
40ºC
≤
Ti1
<
45ºC,
then
the
electrical
heater
maintain
its
original
state.
If
Ti1
≥
45ºC,
then
the
electrical
heater
is
turned
off.
e)
The
range
of
Ts
is
16
‐
30ºC.
f)
Indoor
fan
speed
can
be
adjusted
to
low,
medium,
high
and
auto.
g)
When
turned
on,
MTV2
requires
30
seconds
before
it
is
fully
open.
h)
When
turned
off,
MTV2
requires120
seconds
before
it
is
fully
closed.
Summary of Contents for FDLA-09
Page 1: ...SK2018 GLOBAL FDLA V P AC 001 FDLA V P AC MOTOR...
Page 27: ...Page 26 of 51 SK2018 GLOBAL FDLA V P AC 001 Configuration Settings...
Page 53: ...FDHD V P AC MOTOR...
Page 69: ...B 1 4 4 Electrical connections T Configuration standard version...
Page 74: ...Wiring Diagram D 2 SK NCPDWH 001b S Configuration Full Control PCB...
Page 76: ...Configuration Settings D 3...
Page 111: ......
Page 112: ...SK2019 FCSD H V P ECM 001 FCSD H V P ECM MOTOR...
Page 190: ...SK2019 FCSD H V P ECM 001...
Page 191: ...Page 1 of 59 SK2015 FMCD V EC 001 FMCD ECM MOTOR...
Page 210: ...Page 20 of 59 SK2015 SWC V EC 001 D 1 3 Wiring Diagram SK NCSWC 001...
Page 233: ...Page 43 of 59 SK2015 SWC V EC 001 D 4 2 Wiring diagram SK NCSWC 002...
Page 248: ...Page 58 of 59 SK2015 SWC V EC 001 Troubleshooting Guide E 4...
Page 249: ...Page 59 of 59 SK2015 SWC V EC 001...
Page 250: ...FSTD C V P ECM MOTOR...
Page 256: ...Page 7 of 73 SK2015 FSTDC V P ECM 001 A 2 Unit Appearance FSTDC VAR FSTDC HAR FSTD...