Page
42
of
73
SK2015
FSTDC
‐
V/P
‐
ECM
‐
001
WARNING!
If
the
system
is
turned
off
at
the
circuit
breaker
(or
main
power
supply),
the
drain
pump
will
not
work.
NOTE
When
button
pressing
is
effective,
the
master
unit
buzzer
will
beep
twice
and
the
slave
unit
will
beep
once.
C.11.
Auto
Restart
The
system
uses
non
‐
volatile
memory
to
save
the
present
operation
parameters
when
system
is
turned
off
or
in
case
of
system
failure
or
cessation
of
power
supply.
Operation
parameters
are
mode,
set
temperature,
swing
louver’s
position,
and
the
fan
speed.
When
power
supply
resumes
or
the
system
is
switched
on
again,
the
same
operations
as
previously
set
will
function.
C.12.
On/Off
Switch
On
The
Front
Panel
a)
This
is
a
TACT
switch
to
select
Cool
→
Heat
→
O
ff
opera on
mode.
b)
In
COOL
mode,
the
set
temperature
of
the
system
is
24ºC
with
auto
fan
speed
and
swing.
There
are
no
timer
and
sleep
modes.
c)
In
HEAT
mode,
the
set
temperature
of
the
system
is
24ºC
with
auto
fan
speed
and
swing.
There
are
no
timer
and
sleep
modes.
d)
Master
unit
that
does
not
use
a
wall
pad
will
globally
broadcast.
C.13.
Drain
Pump
Drain
pump
turns
ON
if
the
thermostat
activates
during
cooling
or
dehumidification
cycles.
It
remains
on
for
at
least
5
minutes
after
the
thermostat
stops.
During
mode
change
from
cooling
to
non
cooling
mode,
the
water
pump
will
turn
on
for
a
minimum
of
5
minutes.
C.14.
Float
Switch
Float
‐
switch
opens
before
unit
is
turned
on
If
the
float
switch
(N/C)
is
opened
before
the
unit
is
turned
on,
then
MTV1
is
turned
off.
The
drain
pump
and
indoor
fan
will
operate.
After
float
switch
is
closed,
MTV1
is
turned
on.
Float
switch
is
opened,
when
unit
is
turned
on
If
the
float
switch
is
opened
continuously
≥
5
seconds,
then
the
drain
pump
will
work
and
MTV1
will
remain
off.
After
the
float
switch
is
closed,
the
drain
pump
will
run
for
an
additional
5
minutes.
If
the
float
switch
is
opened
for
10
minutes
continuously,
then
MTV1
will
remain
off.
The
indoor
fan
runs
at
set
speed
and
the
system
reports
an
error.
Float
switch
is
opened,
when
unit
is
turned
off
If
the
float
switch
is
opened,
then
the
drain
pump
will
work.
After
the
float
switch
is
closed,
the
drain
pump
will
run
for
an
additional
5
minutes.
If
the
float
switch
is
opened
for
10
minutes
continuously,
then
the
system
reports
an
error.
C.15.
Electric
Heater
Safety
Switch
a)
Before
the
electrical
heater
is
turned
on,
the
EH
safety
switch
must
be
closed
and
the
fan
RPM
be
more
than
300RPM.If
this
contact
is
opened
for
≥
1
second
or
the
fan
RPM
is
less
than
300RPM,
the
heater
will
be
turned
off
immediately
and
report
an
error.
Once
the
contact
is
returned
to
the
closed
position
≥
60
seconds,
reset
the
error
and
the
heater
will
start
again.
b)
When
the
EH
safety
switch
is
opened
≥
3
times
within
60
minutes,
the
heater
is
not
allowed
to
start
anymore.
Turn
off
the
unit
to
reset
the
fault,
provided
that
the
switch
has
returned
to
the
closed
position.
Summary of Contents for FDLA-09
Page 1: ...SK2018 GLOBAL FDLA V P AC 001 FDLA V P AC MOTOR...
Page 27: ...Page 26 of 51 SK2018 GLOBAL FDLA V P AC 001 Configuration Settings...
Page 53: ...FDHD V P AC MOTOR...
Page 69: ...B 1 4 4 Electrical connections T Configuration standard version...
Page 74: ...Wiring Diagram D 2 SK NCPDWH 001b S Configuration Full Control PCB...
Page 76: ...Configuration Settings D 3...
Page 111: ......
Page 112: ...SK2019 FCSD H V P ECM 001 FCSD H V P ECM MOTOR...
Page 190: ...SK2019 FCSD H V P ECM 001...
Page 191: ...Page 1 of 59 SK2015 FMCD V EC 001 FMCD ECM MOTOR...
Page 210: ...Page 20 of 59 SK2015 SWC V EC 001 D 1 3 Wiring Diagram SK NCSWC 001...
Page 233: ...Page 43 of 59 SK2015 SWC V EC 001 D 4 2 Wiring diagram SK NCSWC 002...
Page 248: ...Page 58 of 59 SK2015 SWC V EC 001 Troubleshooting Guide E 4...
Page 249: ...Page 59 of 59 SK2015 SWC V EC 001...
Page 250: ...FSTD C V P ECM MOTOR...
Page 256: ...Page 7 of 73 SK2015 FSTDC V P ECM 001 A 2 Unit Appearance FSTDC VAR FSTDC HAR FSTD...