Components
Service manual
125
(A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D +
(A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C +
(A)RXF20~42D + (A)RXF20~42E
Split Sensira R32
ESIE18-12G – 2023.01
1×
2
1
2
3×
2
2
1
1
1
To remove the top plate
INFORMATION
This procedure is just an example and may differ on some details for your actual unit.
Prerequisite:
Stop the unit operation via the user interface.
1
Turn OFF the respective circuit breaker.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2
Loosen and remove the screws that fix the top plate.
a
b
a
a
a
a
a
a
Screw
b
Top plate
3
Remove the top plate.