Components
Service manual
94
(A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D +
(A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C +
(A)RXF20~42D + (A)RXF20~42E
Split Sensira R32
ESIE18-12G – 2023.01
All LED’s of the inverter analyzer are lit
during inverter test?
Action
Yes
of the main PCB and continue with the
next procedure.
No
To check the fuse of the main PCB
(A)RXF20~35A + RXF20+25B + (A)RXF20~42C + (A)RXF42D units
Prerequisite:
First perform all earlier main PCB checks, see
89].
1
Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
a
a
Fuse
Blown fuse on the main PCB?
Action
Yes
No
of the main PCB and continue with the
next procedure.
(A)RXF20~35D + (A)RXF20~42E units
Prerequisite:
First perform all earlier main PCB checks, see
89].
1
Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.