Components
Service manual
113
(A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D +
(A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C +
(A)RXF20~42D + (A)RXF20~42E
Split Sensira R32
ESIE18-12G – 2023.01
2
Install the main PCB in the correct location in the switch box.
j
j
k
f
g
a
b
d
c
e
h
h
i
j
j
j
j
j
a
Power supply wires from X1M
b
Ferrite core (power supply wires)
c
Tie strap (power supply wires)
d
Screw (ground wiring)
e
Ferrite core (ground wiring)
f
Connector X12A
g
Compressor connector
h
Tie strap (compressor harness)
i
Ferrite core (compressor harness)
j
Screw
k
Main PCB
3
Install and tighten the screws.
4
Fix the ferrite core (for compressor harness) to the switch box (fixation plug).
5
Install new tie straps to fix the compressor harness to the switch box.
6
Install the ground wiring on the switch box and fix using the screw.
7
If applicable: Connect the connector X12A.
8
Fix the ferrite core (for power supply wiring) to the switch box (fixation plug).
9
Connect the power supply wiring to the main power supply terminal X1M.
10
Fix the power supply wiring to the switch box using a new tie strap.
11
Connect all other connectors to the main PCB.
INFORMATION
Use the wiring diagram and connection diagram for correct installation of the
connectors, see
Is the problem solved?
Action
Yes
No further actions required.
No
Return to
106] of the PCB and
continue with the next procedure.