3
|
Components
Service manual
68
(A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D +
(A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C +
(A)RXF20~42D + (A)RXF20~42E
Split Sensira R32
ESIE18-12G – 2023.01
2
Connect the Faston connectors to the compressor thermal protector.
a
b
c
a
Compressor thermal protector
b
Faston connector
c
Bracket
3
Install the compressor thermal protector in the compressor housing.
4
Install the wire terminals cover on the compressor.
a
a
Compressor wire terminals cover
5
Install the compressor insulation.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
3.4 Expansion valve
3.4.1 Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.