Fuse FU3
Blown fuse on the main PCB?
Action
Yes
Replace the main PCB, see
101].
No
Return to
of the main PCB and continue with the
next procedure.
To check the rectifier voltage of the main PCB
Prerequisite:
First perform all earlier main PCB checks, see
1
Turn ON the power of the unit.
2
Measure the voltage on the rectifier voltage check terminals (+ and –) on the
main PCB.
Result:
The measured voltage MUST be approximately 324 V DC.
b
a
A
A
(A)RXF20~35A + RXF20+25B + (A)RXF20~42C + (A)RXF42D units
a
+ terminal
b
– terminal