3
|
Components
Service manual
140
(A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D +
(A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C +
(A)RXF20~42D + (A)RXF20~42E
Split Sensira R32
ESIE18-12G – 2023.01
3
Disconnect the connector from the swing flap motor.
4
Remove the screw from the swing flap motor.
5
Remove the swing flap motor from the coupling piece.
6
To install the swing flap motor, see
139].
To install the swing flap motor
1
Install the swing flap motor in the correct location on the indoor unit. Make
sure the swing flap motor shaft is correctly inserted in the coupling piece.
a
b
c
a
Cover
b
Screw
c
Swing flap motor
2
Install and tighten the screw to fix the swing flap motor.
3
Connect the connector to the swing flap motor.
4
Install the cover.
5
Install both swing flaps in the indoor unit (by clicking it on).
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
3.13 Thermistors
3.13.1 Refrigerant side thermistors
Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a mechanical check of the specific thermistor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
124].