3
|
Components
Service manual
90
(A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D +
(A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C +
(A)RXF20~42D + (A)RXF20~42E
Split Sensira R32
ESIE18-12G – 2023.01
Does the unit receive power?
Action
Yes
No
Adjust the power supply to the unit, see
154].
(A)RXF20~35D + (A)RXF20~42E units
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
124].
1
Turn ON the power of the unit.
2
Measure the voltage between pins 1‑2 of the connector S10 on the main PCB.
Result:
The measured voltage MUST be 230 V AC.
a
a
Connector S10
Is the measured voltage on the PCB
correct?
Action
Yes
of the PCB and continue with the next
procedure.
No
Continue with the next step.
3
Check the power supply to the unit, see
Does the unit receive power?
Action
Yes
Correct the wiring from the main power
supply terminal to the main PCB, see
101].
No
Adjust the power supply to the unit, see
154].
To check the HAP LED of the main PCB
Prerequisite:
First check the power supply to the main PCB, see
89].
1
Locate the HAP LED on the main PCB.