Components
Service manual
88
(A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D +
(A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C +
(A)RXF20~42D + (A)RXF20~42E
Split Sensira R32
ESIE18-12G – 2023.01
Is the problem solved?
Action
Yes
No further actions required.
No
84] of the indoor unit
main PCB and continue with the next
procedure.
To remove a fuse of the indoor unit main PCB
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
124].
1
Remove the fuse from the PCB.
a
a
Fuse
2
To install a fuse on the indoor unit PCB, see
86].
To install a fuse on the indoor unit main PCB
1
Install the fuse on the correct location on the PCB.
CAUTION
Make sure the fuse is plugged‑in correctly (contact with the fuse holder).
a
a
Fuse
Is the problem solved?
Action
Yes
No further actions required.