3
|
Components
Service manual
75
(A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D +
(A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C +
(A)RXF20~42D + (A)RXF20~42E
Split Sensira R32
ESIE18-12G – 2023.01
CAUTION
Overheating the valve will damage or destroy it.
7
After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
a
b
c
a
Putty
b
Expansion valve pipe
c
Expansion valve body
a
b
a
Expansion valve pipe
b
Expansion valve body
INFORMATION
The expansion valve and coil can have a different configuration / layout.
8
Reinstall the putty.
9
To install the expansion valve coil, see
10
Perform a pressure test, see
155].
11
Add
refrigerant
to
the
refrigerant
circuit,
see
159].
About the installation of the expansion valve motor
NOTICE
Select the correct type.