Components
Service manual
63
(A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D +
(A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C +
(A)RXF20~42D + (A)RXF20~42E
Split Sensira R32
ESIE18-12G – 2023.01
a
a
a
Compressor pipe
CAUTION
Overheating the compressor pipes (and the oil inside the compressor pipes) will
damage or destroy the compressor.
9
After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
10
Install the compressor thermal protector, see
67].
11
Connect the Faston connectors to the compressor wire terminals U, V and W
V
U
W
U
Wire terminal U
V
Wire terminal V
W
Wire terminal W
12
Install the cover of the compressor wire terminals.