SiME281906E
Field Settings with Remote Controller
Part 5 Field Settings and Test Operation
72
Note(s)
1.4 List of Field Settings for Indoor Unit
: Factory setting
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so
they cannot be set individually. Setting changes also cannot be checked.
3. Do not make settings other than those described above. Nothing is displayed for functions
the indoor unit is not equipped with.
4.
88
or
Checking the connection. Please stand by
. may be displayed to indicate the remote
controller is resetting when returning to the normal mode.
5. BRC1H81 series only
Mode
No.
(Note 2)
First
Code
No.
Description
Second Code No.
Page
Reference
01
02
03
04
10 (20)
0
Filter cleaning
sign interval
Long life
filter
Approx.
2,500 hrs.
Approx.
1,250 hrs.
—
—
Ultra
long life
filter
Approx.
10,000 hrs.
Approx.
5,000 hrs.
—
—
1
Filter type
Long life
filter
Ultra long life
filter
—
—
2
Thermistor selection
Remote
cont
Suction air
thermistor
Suction air
thermistor
—
Remote
controller
thermistor
3
Filter cleaning sign
Displayed
Not displayed
—
—
11 (21)
0
Setting number of the
connected indoor units as
simultaneous operation
system
Pair system
(1 unit)
Simultaneous
operation
system
(2 units)
Simultaneous
operation
system
(3 units)
Double twin
multi (4 units)
1
Simultaneous operation
system individual setting
Unified
setting
Individual
setting
—
—
2
Fan ON/OFF at thermostat
OFF (Cooling)
Keep
operating
Stop
—
—
7
Airflow adjustment
OFF
Completion of
airflow
adjustment
Start of airflow
adjustment
—
12 (22)
1
External ON/OFF input
Refer to the page on the right for details.
5
Auto restart after power
failure reset
Disabled
Enabled
—
—
6
Airflow Setting when
cooling thermostat is OFF
LL tap
Set fan
speed
—
—
13 (23)
6
External static pressure
Refer to the page on the right for details.
15 (25)
3
Drain pump and humidifier
interlock selection
Not
interlocked
Interlocked
—
—
5
Selection for individual
ventilation setting by
remote controller
— (Normal)
Individual
—
—
1b
4
Display of error codes on
the remote controller
—
Two-digit
display
—
Four-digit
display
1c
0
Room temperature display
Not displayed
Displayed
—
—
01
(Note 5)
Thermostat sensor
Indoor unit
thermistor
Controller
thermistor
—
—
—
12
(Note 5)
Window contact B1
Do not use
Use
—
—
—
13
(Note 5)
Key card contact B2
Do not use
Use
—
—
—
1e
(Note 5)
02
Setback function
No Setback
Heating only
Cooling only
Heating and
Cooling
—