Troubleshooting by Error Code
SiME281906E
155
Part 6 Service Diagnosis
Note(s)
5.21 High Pressure Switch System Abnormality
Applicable
Models
All outdoor unit models
Error code
H3
Method of Error
Detection
The protection device circuit checks continuity in the high pressure switch.
Error Decision
Conditions
There is no continuity in the high pressure switch when the compressor stops operating.
Supposed
Causes
Defective high pressure switch
Defective connection of high pressure switch connector
Defective outdoor unit main PCB
Disconnected lead wire
Troubleshooting
1. Connector
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Connect the connector correctly.
Is high
pressure switch
connector (
∗
1) correctly
connected to outdoor unit
main PCB?
For 18/24 class :
Proceed to
H5
troubleshooting.
For remaining outdoor units:
Replace the outdoor unit main PCB
(A1P).
NO
Wait for 10 minutes after the unit
stops operating, then check the
following.
YES
Replace the high pressure switch
with no continuity.
Resistance in normal operation:
10
Ω
or less
Is there
continuity in each high
pressure switch?
NO
YES
Replace the lead wire.
Is there continuity in
lead wire?
NO
YES
High pressure switch
Connector for high pressure switch
Activation pressure
S1PH
X32A
4.15 MPa