Troubleshooting by Error Code
SiME281906E
153
Part 6 Service Diagnosis
5.20 Discharge Pipe Temperature Abnormality
Applicable
Models
All outdoor unit models
Error code
F3
Method of Error
Detection
The error is detected according to the temperature detected by the discharge pipe
thermistor.
The error is detected if there is an abnormality in the self-operating thermal protector.
Error Decision
Conditions
The discharge pipe temperature rises to an abnormally high level.
The discharge pipe temperature rises suddenly.
The discharge pipe temperature does not rise after operation start.
Supposed
Causes
Defective discharge pipe thermistor
Defective connection of discharge pipe thermistor connector
Refrigerant shortage
Defective compressor
Disconnection of discharge pipe thermistor from discharge pipe
Defective outdoor unit main PCB