Troubleshooting by Error Code
Part 6 Service Diagnosis
166
5.28 Compressor Startup Abnormality
Applicable
Models
All outdoor unit models
Error code
L9
Method of Error
Detection
The error is detected by converting the current flowing to power transistor into voltage with CT1
(DC current sensor).
Outdoor unit main PCB detects the disorder of position signal.
Error Decision
Conditions
When overload or load fluctuation is detected at compressor startup.
Supposed
Causes
The stop valve is not opened.
Defective wiring between compressor and inverter
Defective compressor wiring, compressor open phase
Pressure differential startup (0.9 MPa or more)
Defective outdoor unit main PCB
Defective compressor (lock)
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Open the stop valve.
Is the stop valve open?
NO
NO
YES
Mount the compressor lead
wire.
Compressor lead
wire is detached.
YES
NO
Check the installation conditions.
Insufficient pressure
equalization.
Check refrigerant system.
Is the
difference between
high and low pressure before
startup less than 0.2
MPa?
YES
A
Go to the next page