Troubleshooting by Error Code
Part 6 Service Diagnosis
178
Reference
Reference
Troubleshooting
RZF30/36AVMK
CHECK 4
Refer to page 196.
CHECK 7
Refer to page 198.
Correct the power supply voltage.
Is the power
supply voltage within the
normal range?
NO
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Are the resistance
values between pins balanced
within ±20%?
YES
YES
Remove the fan motor connector from
the PCB and start operation.
Replace the fan motor.
Does error code
U2
recur?
Is the fan motor
operating normally? (Refer
to
E7
troubleshooting
flowchart)
NO
NO
YES
YES
CHECK 7
Replace the outdoor unit main PCB
(A1P).
NO
Monitor the voltage. (Instantaneous
voltage drop)
(Voltage fluctuation due to an in-house
generator)
YES
Is the
measured voltage 220
VDC or more?
While the compressor is running,
measure the voltage between C+ and
C– of power module.
Replace the outdoor unit main PCB
(A1P).
Connect the fan motor and
operate?
NO
YES
Connect the wires correctly.
Are the power
supply and compressor
connections correct? Is
there open
phase?
NO
YES
CHECK 4
Replace the fan motor.