Part 6 Service Diagnosis
6.8 Clogged Points Check
CHECK 10
Temperature differences must occur before or after the clogged points.
(1)
(3)
(3)
(5)
(4)
Indoor unit
Outdoor unit
(2)
COMP
ACC
Check points
Check factor
Causes
Remedies
1
Around expansion
mechanism
Temperature
difference
Dust
Choked moisture
Reduced effective pipe diameter due
to adherent contamination, etc.
Replace the electronic expansion
valve.
2
Accumulator for
compressor
Frosting
Choked moisture
Blow nitrogen gas, and then replace
the refrigerant.
3
Distributor
Temperature
difference
Dust
Choked moisture
Reduced effective pipe diameter due
to adherent contamination, etc.
Replace the heat exchanger or
distributor.
4
Field piping
Temperature
difference
Collapsed pipe
Replace the pipe.
5
Stop valve
Temperature
difference
The stop valve is not fully open.
Open the stop valve fully.