Troubleshooting with LED Indications
SiME281906E
117
Part 6 Service Diagnosis
Note(s)
Note(s)
3. Troubleshooting with LED Indications
3.1 Indoor Unit
Troubleshooting can be carried out by service monitor LED (green). (Blinks when normal)
k
: LED ON /
h
: LED OFF /
l
: LED blinks
1. Operation halts due to error depending on the model or condition.
2. Troubleshoot by turning OFF the power supply for a minimum of 5 seconds, turning it back
ON, and then rechecking the LED display.
3.2 Outdoor Unit
3.2.1 RZF18/24AVMK
The following diagnosis can be conducted by turning ON the power switch and checking the
LED indication on PCB (A1P) of the outdoor unit.
k
: LED ON /
h
: LED OFF /
l
: LED blinks
1. Turn OFF the power supply, and turn it ON again after 5 seconds or more. Check the error
condition, and diagnose the problem.
2. Turn OFF the power supply. After 5 seconds or more, disconnect the transmission wiring for
indoor unit. Then turn ON the power supply. If the HAP on the outdoor unit main PCB blinks
after about 10 seconds, the indoor unit PCB is defective.
3. Also check for open phase.
Remark:
The error history continues to indicate the previously generated error until the power supply is
turned OFF. Be sure to turn OFF the power supply after inspection.
Service monitor
LED
Description
HAP (Green)
l
Indoor unit normal
Outdoor unit troubleshooting
l
Incorrect transmission wiring between indoor and outdoor unit
If outdoor unit’s HAP is OFF, proceed outdoor unit’s troubleshooting. If outdoor
unit’s HAP blinks, defective wiring or indoor or outdoor unit PCB.
k
Defective indoor unit PCB
h
Defective power supply or defective PCB or broken transmission wire between
indoor and outdoor unit.
Service monitor
Description
HAP
(Green)
H1P
(Orange)
l
h
Normal
k
—
Defective outdoor unit main PCB (Note 1)
h
—
Power abnormality or outdoor unit main PCB malfunction (Note 2)
l
k
Activation of protection device (Note 3)