Troubleshooting by Error Code
SiME281906E
187
Part 6 Service Diagnosis
Troubleshooting
Use the correct combination.
Is the indoor
unit and outdoor unit
combination correct?
NO
Use only one remote controller.
YES
Are
multiple indoor units
connected to the remote
controller?
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
YES
Remove wiring.
(Group control within the same system
is not possible)
Is the remote
controller wired between
indoor units?
YES
NO
Operating normally?
NO
Correct the wiring.
Is the indoor-indoor
and indoor-outdoor wired
correctly?
Is there 220-240
VAC between 1-2 of
terminal block (X2M) of
indoor unit?
Are the
service monitors
(HAP) of all indoor unit PCB
blinking?
NO
NO
NO
Connect the PCB correctly.
YES
Check the power system within the
indoor unit.
NO
NO
Connect the wiring correctly.
Wiring could be incorrect, recheck.
NO
Replace the indoor unit PCB.
YES
YES
Is the PCB
correctly connected?
Is the indoor-indoor
and indoor-outdoor wired
correctly?
YES
NO
Connect the power supply correctly.
Is power
supply for optional
devices taken from between
terminal blocks 1-2 of the
indoor/outdoor relay terminal
block (X2M)?
YES
YES
Operates normally.
YES
Turn the power OFF once, then
restart operation.