Troubleshooting by Error Code
Part 6 Service Diagnosis
134
5.7 Fan PCB Abnormality
Applicable
Models
All indoor unit models
Error Code
A8
Method of Error
Detection
Microcomputer checks the voltage state of the fan PCB.
Error Decision
Conditions
Overvoltage or voltage drop is detected on the fan PCB.
Supposed
Causes
Defective connection of the power supply connector
Defective indoor unit PCB
Defective fan PCB
External factor such as noise
Troubleshooting
Check for the indoor unit control
PCB (A1P) and the fan PCB
(A2P).
Connect the connector correctly.
NO
YES
YES
YES
NO
NO
Is the
connector X3A on the
fan PCB connected
correctly?
Connect the connector correctly.
NO
Is the
connector X70A on the
indoor unit control PCB
connected correctly?
Replace the harness.
YES
Is the
harness connecting
X3A and X70A broken?
Remove the external factor.
YES
Is there any
external factor such as
noise?
Normal.
NO
Error is
displayed again.
Turn OFF the power supply and
then turn it ON again.
↓
Start operation with the remote
controller.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.