Field Settings from Outdoor Unit PCB (For 30/36 Class)
SiME281906E
85
Part 5 Field Settings and Test Operation
3.3.2 Overview of Monitor Mode (Mode 1)
1: Numbers in the "No." column represent the number of times to press the BS button.
No.
(
1)
Item
Contents
Description
Display
Description
Display
SEG 1 SEG 2 SEG 3
SEG 1 SEG 2 SEG 3
0
Display of quiet
operation
1
0
0
Constantly
Low noise level 1
Low noise level 2
Low noise level 3
0
1
2
3
1
Display of demand
operation
1
0
1
Constantly
Demand level 1
Demand level 2
Demand level 3
0
1
2
3
2
Display of oil return
control
1
0
2
Constantly
During oil return control
0
1
4
Error content
(updated)
1
0
4
Display of the error code and the detailed code
5
Error content
(previous error)
1
0
5
6
Error content
(the one before
previous)
1
0
6
9
Drop factor
1
0
9
Normal
In the low voltage drop
In the high voltage drop
In the inverter suction pipe drop
In the inverter current drop
In the FIN temperature drop
In the inverter drop
In the comprehensive current drop
Others
0
1
2
3
5
6
7
8
9