Symptom-Based Troubleshooting
SiME281906E
111
Part 6 Service Diagnosis
Reference
CHECK 2
Refer to page 195.
Does indoor unit
airflow rate decrease?
YES
Check each section.
• Soiled heat exchanger
• Defective fan motor
(Refer to troubleshooting
A6
.)
Check each item.
• Refrigerant overcharge
• Air mixed in refrigerant system
• Soiled heat exchanger
• Short circuit of discharge air
• Disturbing item in airflow
• Defective fan motor of outdoor unit
(Refer to troubleshooting
E7
.)
Check each item.
• Insufficient compression of
compressor
• Insufficient circulation of refrigerant
• Defective electronic expansion valve
NO
Is the level of
high pressure higher than
normal level?
YES
NO
CHECK 2
A