
Symptom-Based Troubleshooting
SiME281906E
105
Part 6 Service Diagnosis
Note(s)
1. Blinking pattern: 0.2 seconds ON, 0.2 seconds OFF (blinking approximately 25 times in 10
seconds)
(Normally 0.4 seconds ON, 0.4 seconds OFF (blinking approximately 12 times in 10 seconds))
Normal. Start up operation after 3
minutes (3-minute standby).
Is the thermostat
changed and reset again?
YES
NO
Diagnose based on error code on
remote controller.
Is the
operation lamp on
LCD remote controller
blinking?
YES
NO
Diagnose based on error code on
remote controller.
Is the
operation lamp on
indoor unit signal receiving part
blinking?
YES
NO
Replace the fuse (F1U).
The fuse (F1U) on the outdoor
unit PCB is blown.
YES
NO
Check the electric system.
• The fan motor and fan PCB
may have failed simultaneously, so
be sure to check both.
Defective electric component
A