Troubleshooting by Error Code
Part 6 Service Diagnosis
154
Reference
Troubleshooting
CHECK 1
Refer to page 192.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Abnormality in refrigerant
system such as refrigerant
shortage, defective
compressor, etc.
Conduct inspection.
Is the
discharge
pipe temperature
higher than 110°C or the
compressor self-operating
thermal protector
temperature higher
than 120°C?
YES
Replace the discharge pipe
thermistor.
Is the discharge pipe
thermistor characteristic
normal?
Replace the outdoor unit main
PCB (A1P).
NO
YES
NO
Connect the thermistor
correctly.
Is the
discharge pipe
thermistor correctly connected to
outdoor unit main PCB?
NO
YES
Attach the thermistor properly.
Is the discharge
pipe thermistor attached to the
discharge pipe?
NO
YES
CHECK 1