Check
SiME281906E
197
Part 6 Service Diagnosis
6. Use a multimeter to measure the resistance listed in the table.
Among the three phases listed in the table, if there is one phase with unbalanced resistance
(with a value five times higher than the other values), then the power transistor is defective.
When normal, all phases have the same resistance value.
Multimeter
Resistance
Multimeter
Resistance
Red (+)
Black (–)
Red (+)
Black (–)
C+
U
C–
U
C+
V
C–
V
C+
W
C–
W
U
C+
U
C–
V
C+
V
C–
W
C+
W
C–
红
Blue
White
Red
Outdoor unit PCB
Compressor