Troubleshooting by Error Code
SiME281906E
149
Part 6 Service Diagnosis
Reference
Troubleshooting
RZF30/36AVMK
CHECK 7
Refer to page 198.
Is the fan
motor connector
correctly connected to the
outdoor unit main PCB?
(X106A)
YES
NO
Properly connect the
connector.
Turn OFF the power (and wait for 10
minutes).
Does the fuse F6U
have continuity?
NO
YES
Replace the fuse.
Use only specified fuse.
Is there any foreign
matter around the
fan?
NO
YES
Remove the foreign matter.
Is the fan rotatable easily
by hand?
Remove the fan motor connector. (X106A)
YES
NO
Replace the fan motor.
CHECK 7
Are the
resistance values between pins
balanced within ±20%?
YES
Replace the outdoor unit main
PCB (A1P).
(The fan motor is not defective.)
If the
E7
error recurs even so:
The device is not at fault.
The failure may be caused by
external factors (such as
noise).
Completed.
(The fan motor was defective.)
If the
E7
error recurs even so:
The device is not at fault.
The failure may be caused by
external factors (such as
noise).
Replace the outdoor unit main
PCB (A1P).
(The fan motor and the
outdoor unit main PCB (A1P)
were defective.)
Check the resistance value for the
fan motor.
NO
Replace the fan motor.
Does the error recur?
YES
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.