Field Settings with Remote Controller
Part 5 Field Settings and Test Operation
78
Make sure that 11(21)-7 (Airflow adjustment) is set to
01
(OFF).
1.5.12 Drain Pump and Humidifier Interlock Selection
This is used to interlock the humidifier with the drain pump. When water is drained out of the
unit, this setting is unnecessary.
: Factory setting
1.5.13 Selection for Individual Ventilation Setting by Remote Controller
This is set to perform individual operation of heat reclaim ventilation using the remote
controller/central unit when heat reclaim ventilation is built in.
(Switch only when heat reclaim ventilation is built in.)
: Factory setting
1.5.14 Display of Error Codes on the Remote Controller
BRC1E Series
Error code (four digits) is displayed for limited products. Select two-digit display if four-digit
display is not preferred.
: Factory setting
1.5.15 Room Temperature Display
BRC1E Series
A "Detailed display screen" can be selected as the display screen. This setting is used if you do
not want to display "Room temperature display" on the "Detailed display screen".
: Factory setting
FDMF36AVMK
: Factory setting
Mode
No.
First Code
No.
Second
Code No.
Contents
13 (23)
6
05
50 Pa
06
60 Pa
07
70 Pa
08
80 Pa
09
90 Pa
10
100 Pa
Mode
No.
First Code
No.
Second
Code No.
Contents
15 (25)
3
01
Not interlocked
02
Interlocked
Mode
No.
First Code
No.
Second Code
No.
Contents
15 (25)
5
01
— (Normal)
02
Individual
Mode
No.
First
Code No.
Second
Code No.
Contents
1b
4
01
―
02
Two-digit display
03
―
04
Four-digit display
Mode
No.
First
Code No.
Second
Code No.
Contents
1c
0
01
Not displayed
02
Displayed