Troubleshooting by Indication on the Remote Controller
SiUS28-902_a
127
Troubleshooting
3.33 “
LC
” Outdoor Unit: Malfunction of Transmission
between Inverter and Control P.C.B.
Remote
Controller
Display
LC
Applicable
Models
RZQ18~30PVJU
Method of
Malfunction
Detection
Check the communication state between inverter P.C.B. and control P.C.B. by micro-computer.
Malfunction
Decision
Conditions
When the correct communication is not conducted in certain period.
Supposed
Causes
Malfunction of connection between the inverter microcomputer and outdoor control
microcomputer
Defect of outdoor unit P.C.B.
Defect of noise filter
External factor (Noise etc.)
Troubleshooting
Caution
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting
the connector, or parts co
u
ld
b
e damaged.
Is "
E7
"
displayed on the remote
controller? (not "
LC
")
Disconnect the connection for
the fan motor, and t
u
rn on
again.
Replace the o
u
tdoor
u
nit P.C.B.
(A1P).
Replace the fan motor.
Fail
u
re of the in
v
erter
transmission occ
u
rs d
u
e to the
fan motor malf
u
nction.
YES
YES
N
O
Is the
connector for the
fan motor properly
connected to the indoor
u
nit P.C.B.?
Connect correctly.
N
O
Summary of Contents for SkyAir FCQ18PVJU
Page 1: ...Split System Air Conditioners SkyAir Inverter R 410A Heat Pump 60Hz P Series SiUS28 902_a...
Page 44: ...Other Control SiUS28 902_a 37 Function...
Page 81: ...SiUS28 902_a Troubleshooting by Remote Controller Troubleshooting 74...
Page 185: ...SiUS28 902 Precautions for New Refrigerant R 410A Precautions for New Refrigerant R 410A 178...