Specifications
SiUS28-902_a
7
Specifications
1.3
FAQ
Wall Mounted Type
Notes:
1. The above data are based on the following conditions.
2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Model
Indoor unit
FAQ18PVJU
FAQ24PVJU
Outdoor unit
RZQ18PVJU
RZQ24PVJU
Power supply
1 phase 60Hz 208-230V
1 phase 60Hz 208-230V
Cooling capacity ¹
Btu/h
18,000
24,000
Heating capacity ²
Btu/h
20,000
26,000
Indoor unit
FAQ18PVJU
FAQ24PVJU
Color
White (3.0Y8.5/0.5)
White (3.0Y8.5/0.5)
Dimensions
H×W×D
in (mm)
11–3/8 × 41–3/8 × 9 (290 x 1050 x 230)
11–3/8 × 41–3/8 × 9 (290 x 1050 x 230)
Coil
Type
Cross fin coil
Cross fin coil
Rows×Stages×FPI
2 × 14 × 18
2 × 14 × 18
Face area
ft²
2.29
2.29
Fan
Model
QCL9686M
QCL9686M
Type
Crossflow fan
Crossflow fan
Motor output
W
43
43
Airflow rate (H/L)
cfm
500/400
635/470
Air filter
Resin net (Washable)
Resin net (Washable)
Mass (Weight)
lb (kg)
31 (14)
31(14)
Piping
connections
Liquid
in (mm)
φ
3/8 (9.5) (Flare connection)
φ
3/8” (9.5) (Flare connection)
Gas
in (mm)
φ
5/8 (15.8) (Flare connection)
φ
5/8” (15.8) (Flare connection)
Drain
in (mm)
VP13 External dia. 11/16 (17.5)
Internal dia. 1/2 (12.7)
VP13 External dia. 11/16”(17.5)
Internal dia. 1/2 (12.7)
Remote controller (option)
Wired
BRC1D71
BRC1D71
Wireless
BRC7E818
BRC7E818
Outdoor unit
RZQ18PVJU
RZQ24PVJU
Color
Ivory
Ivory
Dimensions
H×W×D
in (mm)
30–5/16 × 35–7/16 × 12–5/8
(770 x 900 x 320)
30–5/16 × 35–7/16 × 12–5/8
(770 x 900 x 320)
Coil
Type
Cross fin coil
Cross fin coil
Rows×Stages×FPI
2 × 34 × 18
2 × 34 × 18
Face area
ft²
7.1
7.1
Comp.
Model
2YC63HXD#ED
2YC63HXD#ED
Type
Hermetically sealed swing type
Hermetically sealed swing type
Motor output
kW
1.7
1.7
Fan
Model
P47N11F
P47N11F
Type
Propeller fan
Propeller fan
Motor output
W
70
70
Airflow rate
cfm
1,835
1,835
Mass (Weight)
lb (kg)
150 lbs (67)
150 lbs (67)
Piping
connections
Liquid
in (mm)
φ
3/8 (9.5) (Flare connection)
φ
3/8 (9.5) (Flare connection)
Gas
in (mm)
φ
5/8 (15.8) (Flare connection)
φ
5/8 (15.8) (Flare connection)
Drain
in (mm)
φ
1 (25.4) (Hole)
φ
1 (25.4) (Hole)
Safety devices
High pressure switch.
Outdoor fan driver overload protector.
Thermal protector for indoor fan motor.
Inverter overload protector.
Fusible plugs. Fuse.
High pressure switch.
Outdoor fan driver overload protector.
Thermal protector for indoor fan motor.
Inverter overload protector.
Fusible plugs. Fuse.
Capacity step
%
100-0
100-0
Refrigerant control
Electronic expansion valve
Electronic expansion valve
Ref. piping
Standard length
ft (m)
25’ (7.5)
25’ (7.5)
Max. length
ft (m)
164’ (50)
164’ (50)
Max. height difference
ft (m)
98’ (30)
98’ (30)
Refrigerant
Model
R410A
R410A
Charge (factory charge)
Lbs (kg)
5.1 (2.3)
5.1 (2.3)
Ref. oil
Model
Refer to the name plate of compressor.
Refer to the name plate of compressor.
Charge
L
0.75
0.75
Drawing Number
C : 4D062151D
C : 4D062151D
Cooling
∗
1
Heating
∗
2
Equivalent Piping Length
Hz, Volts
Indoor : 80°FDB, 67°FWB
Outdoor : 95°FDB
Indoor : 70°FDB
Outdoor : 47°FDB, 43°FWB
25 ft (7.5 m) (Level Difference : 0)
60Hz, 230V
Summary of Contents for SkyAir FCQ18PVJU
Page 1: ...Split System Air Conditioners SkyAir Inverter R 410A Heat Pump 60Hz P Series SiUS28 902_a...
Page 44: ...Other Control SiUS28 902_a 37 Function...
Page 81: ...SiUS28 902_a Troubleshooting by Remote Controller Troubleshooting 74...
Page 185: ...SiUS28 902 Precautions for New Refrigerant R 410A Precautions for New Refrigerant R 410A 178...